In Line Check Valves
Suitable for all standard refrigerants such as R-12,R-22,R-502,R-717,R-134a.These in line check valves are designed to provide refrigerant flow control to hot gas lines, compressor discharge lines, suction lines, and hot gas heated drain pan. These valves are not recommended for slow speed compressor discharge lines or for any compressor discharge where a low speed machine discharges into the same downstream header, or for use on side port suction lines on a screw compressor installation.
FEATURES:
- Can be installed in any position
- Stainless steel internal ports
- Lapped metal seat
- Low pressure drop
- Compact size occupies very little space
INSTALLATION:
Valve may be located in any position. Arrow on valve body should match direction of flow. Secure valve with gaskets between flanges and tighten bolts evenly. Do not use this valve or any component to align pipes or gap between flanges.
Do not install on inlet side of solenoid valves or control valves with electric shutoff or shut-off valves unless a relief valve is used from therein between piping.